기술문의

질문하기

ieocr-mme 제품을 설치 중인데 설정에 따라 TRIP 접점을 어떻게 구성해야 하는지요?

mme 제품의 경우 SYScF 메뉴에 out 설정과 oP 설정에 따라 trip시 출력이 변경 됩니다.



아래 표를 참조 부탁 드립니다.
Non ZCT Type : MMED
Built in : MMEB
External ZCT : MMEZ

 
Type Output Function Ready Run(Y) Run(D) Stop Alarm Fault Fault Reset
Non ZCT Type- DOL O1 Control Open Close   Open Close Open Open
O2 ALo “A” Open Close   Open Close Open Open
ALo “F” Open Close   Open Flicker *1Flicker II Open
ALo “H” Open Open   Open Close Open Open
O3 Trip Open Open   Open Open Close@OL Open
Non ZCT Type- YD O1 Control Open Close Open Open   Open Open
O2 Control Open Open Close Open   Open Open
O3 Trip Open Open Open Open   Close Open
Built in or External ZCT – DOL with CO O1 Control Open Close   Open Close Open Open
O2 ALo “A” Open Close   Open Close Open Open
ALo “F” Open Close   Open Flicker *1Flicker II Open
ALo “H” Open Open   Open Close Open Open
O3 Trip Open Open   Open Open Close Open
Built in or External ZCT – DOL with SE O1 Control Open Close   Open   Open Open
O2 OL Trip Open Open   Open   Close@OL Open
O3 EF Trip Open Open   Open   Close@EF Open
Built in or External ZCT –  YD with CO O1 Control Open Close Open Open   Open Open
O2 Control Open Open Close Open   Open Open
O3 Trip Open Open Open Open   Close Open
Built in or External ZCT – YD with SE O1 Control Open Close Open Open   Open Open
O2 Control Open Open Close Open   Open Open
O3 EF Trip Open Open Open Open   Close@EF Open
Non ZCT Type Inverter O1 Inverter Open Close   Open   Open Open
O2 N/A Open Open   Open   Open Open
O3 Trip Open Open   Open   Close Open
Non ZCT Type Bypass O1 N/A Open Open   Open   Open Open
O2 Bypass Open Close   Open   Open Open
O3 Trip Open Open   Open   Close Open
Built in or External ZCT – Inverter  with CO O1 Inverter Open Close   Open   Open Open
O2 N/A Open Open   Open   Open Open
O3 Trip Open Open   Open   Close Open
Built in or External ZCT – Inverter  with SE O1 Inverter Open Close   Open   Open Open
O2 N/A Open Open   Open   Open Open
O3 EF Trip Open Open   Open   Close@EF Open
Built in or External ZCT – Bypass  with CO O1 N/A Open Open   Open   Open Open
O2 Bypass Open Close   Open   Open Open
O3 Trip Open Open   Open   Close Open
Built in or External ZCT – Bypass  with SE O1 N/A Open Open   Open   Open Open
O2 Bypass Open Close   Open   Open Open
O3 EF Trip Open Open   Open   Close@EF Open

 
이 도움이 되었습니까?