How to use Premium racks in M580 system

An M580 system allows TSX RKY •EX Premium extended local racks. Using Premium racks in an M580 system allows you to preserve cabling in an existing configuration.

1. Install an M580 CPU on the main local rack.
2. Connect a Modicon X80 extended rack to the main local rack via X Bus extension cable. NOTE: The maximum X Bus cable length between the M580 main local rack and the first
Modicon X80 extended local rack is 30 m (98 ft).
3. Connect a TSX RKY •EX Premium rack to the Modicon X80 extended local rack via X Bus extension cable.
4. If desired, connect a Premium extended rack to the Premium main rack via X Bus extension cable.
NOTE: The maximum X Bus cable length between the M580 main local rack and the last Premium extended local rack is 100 m (328 ft). Maximum cable length between two
racks (X80 rack or Premium rack) is 30 m (98 ft).